The industrial computer has a ground screw on the housing. Is connecting it mandatory, and how is it done correctly?

IPC247 engineering Answered on 2026-09-16
Yes, connect it. The chassis ground lets noise and surges drain to earth instead of passing through the board, and it improves electrical safety for operators. Correct connection: 1. Use adequately sized wire, as short as possible, from the housing screw to the cabinet PE bar. Flat braided strap drains high-frequency noise better than round wire of the same cross-section. 2. If the mounting plate is part of the earth path, scrape paint at the screw point and use a serrated washer for solid contact. 3. Signal cable shields are usually earthed at one end only, to avoid ground loops that cause noise or current flowing on the shield. Many puzzling faults come from poor earthing: offset touch input, USB or COM ports dropping out, random RS-485 errors, the machine hanging when a drive starts. When you see these, check earthing before suspecting the hardware. Note: the plant's earth electrode must meet the resistance required for the electrical installation.

Read more

Related questions

Our cabinet is in a coastal area, and early in the morning there is condensation inside the door. How do we protect the … Our machine has fans because it needs a powerful CPU and expansion cards. How should we maintain fans and dust filters s… The computer is mounted on a CNC machine body and vibrates heavily. How should we select and install it so it lasts? Mounting a 15-inch Panel PC in a cabinet door: what cutout size do we use, and how do we keep the front at IP65? How much clearance does a fanless machine need inside a cabinet, and should it be mounted flat or upright?

Is your case different?

Leave your number — an engineer will call back with advice for your exact situation.

We only use this number to answer your request.